TECHNICAL SPECIFICATIONS
160 kVA / 180 kVA / 200 kVA
PARAMETERS | DG MODELS | ||||||
---|---|---|---|---|---|---|---|
Parameters | DG Model | ||||||
50 Hz Prime | Rating(kVA) | 160 | 180 | 200 | |||
Rated (KWe) | 128 | 144 | 160 | ||||
Engine Model | mPower61995G | mPower62235G | mPower62485G | ||||
No of Cylinders | 6 | 6 | 6 | ||||
Phase / Voltage (V) | 3 / 415 | ||||||
Power Factor | 0.8 (lagging) | ||||||
Current (A) | 115 | 139 | 174 | ||||
Frequency (Hz)& RPM | 50/1500 | ||||||
Governing class | G2 as per ISO 8528 Part V | ||||||
Starting system | 24 V DC Elec | ||||||
Fuel tank capacity | 300 | 300 | 400 | ||||
Canopy dimensions w/o silencer (mm) (L x W x H) approx. | 3750 x 1300 x 1800 | 4500 x 1400 x 1800 | 4500 x 1400 x 1800 | ||||
Genset Weight (kg) approx. | 2350 | 2750 | 2800 | ||||
Engine Specification | |||||||
Make / Series | Mahindra mPower | ||||||
Rated Power at 100% Load @ 1500 RPM (HP) | 199 | 223 | 248 | ||||
Aspiration | Turbocharged Aftercooled | ||||||
Bore x Stroke (mm) | 105 x 137 | 105 x 137 | 105 x 137 | ||||
Displacement (Lit) | 7.2 | 7.2 | 7.2 | ||||
Fuel consumption @ 75% load (lit/hr) ^ | 27.8 | 28.7 | 33.3 | ||||
Fuel consumption @ 100% load (lit/hr) ^ | 36.7 | 38.2 | 40.8 | ||||
Lube oil specification | 15W40 API CI4+ | ||||||
Total lubrication system capacity (lit) | 20.2 | 20.2 | 20.2 | ||||
Lube oil consumption @ 100% load ($) | 0.1% of Fuel Consumption | ||||||
Lube oil change period (hrs.) | 500 | ||||||
Radiator coolant capacity (liter) | 25 | 24 | 24 | ||||
Rated Speed(RPM) | 1500 | ||||||
Rated Engine Power KW (HP) | 146.5 | 163 | 180 | ||||
199 | 221.5 | 244.6 | |||||
Rated Current(AMP) Capacity @ 0.8PF | 1 Phase | NA | |||||
3 Phase | 222.6 | 250.4 | 278.2 | ||||
Cooling System | Water Cooled | ||||||
Door Type | DD | DD | DD | ||||
Dimension | Length | 3750 | 4300 | 4300 | |||
Width | 1300 | 1400 | 1400 | ||||
Height | 1800 | 1800 | 1800 | ||||
Intergrated Fuel Tank Capacity (lits) | 250 | 390 | 390 | ||||
Approximate Weight of DG set (Kg) | 2350 | 2750 | 2800 | ||||
Alternator | |||||||
Enclosure Type | IP23 | ||||||
Voltage regulation | ±1% | ||||||
Class of insulation | Class H | ||||||
Maximum Unbalanced Load across Phases | 25% |